Summary
Successful exploitation of these vulnerabilities could allow a malicious user to access the device and gain administrative access. This access would allow the user to view, edit, and upload configuration files. Further, a malicious user can cause the switch to reboot by navigating to a specific URL on the device. This action can be scripted on the malicious user's local machine to cause continuous rebooting of the switch.
The following versions of Red Lion Controls N-Tron 700 Series are affected:
- 700 Series <=Firmware_3.11.0 (CVE-2026-32645, CVE-2026-39460, CVE-2026-28745, CVE-2026-33367, CVE-2026-29797, CVE-2026-39453, CVE-2026-33272)
- 700 Series <=Bootloader_2.0.6.1 (CVE-2026-32645, CVE-2026-39460, CVE-2026-28745, CVE-2026-33367, CVE-2026-29797, CVE-2026-39453, CVE-2026-33272)
| CVSS | Vendor | Equipment |
|---|---|---|
| v3 8.3 | Red Lion Controls | 700 Series |
| 7 Vulnerabilities |
|---|
| Use of Hard-coded Credentials, Insufficiently Protected Credentials, Storing Passwords in a Recoverable Format, Missing Authentication for Critical Function, Download of Code Without Integrity Check, Reachable Assertion, Authentication Bypass Using an Alternate Path or Channel |
Background
- Critical Infrastructure Sectors: Commercial Facilities, Communications, Critical Manufacturing, Information Technology
- Countries/Areas Deployed: Worldwide
- Company Headquarters Location: Sweden
Vulnerabilities
Expand All + CVE-2026-32645 Default factory credentials with administrative access are enabled and persist even after configuring other administrator accounts. Read More2 Affected Products
Red Lion Controls 700 Series: <=Firmware_3.11.0Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Relevant CWE: CWE-798 Use of Hard-coded Credentials
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 6 | MEDIUM | CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:N |
| 4.0 | 9.2 | CRITICAL | CVSS:4.0/AV:L/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:N/SC:H/SI:H/SA:N |
4 Affected Products
Red Lion Controls 700 Series: <=Firmware_3.11.0Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Relevant CWE: CWE-522 Insufficiently Protected Credentials
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 8.1 | HIGH | CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N |
| 4.0 | 9.3 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:N/SC:H/SI:H/SA:N |
6 Affected Products
Red Lion Controls 700 Series: <=Firmware_3.11.0Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Relevant CWE: CWE-257 Storing Passwords in a Recoverable Format
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 7.5 | HIGH | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
| 4.0 | 9.3 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N |
8 Affected Products
Red Lion Controls 700 Series: <=Firmware_3.11.0Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Relevant CWE: CWE-306 Missing Authentication for Critical Function
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 8.1 | HIGH | CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N |
| 4.0 | 9.3 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:N/SC:H/SI:H/SA:N |
10 Affected Products
Red Lion Controls 700 Series: <=Firmware_3.11.0Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgrade procedure document can be viewed here..
Mitigation
The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here
Product Status: known_affected
RemediationsVendor fix
Red Lion controls recommends the following upgrades for the N-Tron 700 Series:
Mitigation
Upgrade to firmware version 3.11.1 or greater
Mitigation
Configure or disable the SNMP communities
Mitigation
Disable access to the web GUI
Mitigation
The upgra